Baxi Potterton Promax Combi HE Plus A Range Manuel de service

Naviguer en ligne ou télécharger Manuel de service pour Chauffe-eau et chaudières Baxi Potterton Promax Combi HE Plus A Range. Baxi Potterton Promax Combi HE Plus A Range Technical data Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Promax SL

© Baxi Heating UK Ltd 2007Installation & Service InstructionsPromax SLRangeThese instructions include the Benchmark Commissioning Checklistand sho

Page 2 - Commissioning Checklist

Appliance Category CAT I 2H4.0 Technical Data10© Baxi Heating UK Ltd 2007HorizontalFlue Terminal Diameter 110mmDimensions Projection 150mmOutercase D

Page 3 - © Baxi Heating UK Ltd 2007

5.0 Dimensions and Fixings11© Baxi Heating UK Ltd 2007DIMENSIONSA 600mmB 280mmC 390mmD 150mm Ø Min.E 162.5mmF 96mmSIDE FLUE (left and right)For every

Page 4 - Legislation

6.0 System Details12© Baxi Heating UK Ltd 20076.1 Water Circulating Systems1. The appliance is suitable for use with open vent fullypumped systems and

Page 5 - Safe Manual Handling

6.0 System Details13© Baxi Heating UK Ltd 20076.3 Pipework1. The sizes of flow and return pipes from the boiler shouldbe determined by normal methods,

Page 6 - Contents

6.0 System Details14© Baxi Heating UK Ltd 20076.6 System ControlsThis boiler does not require a bypass.This boiler does not require a permanent live.T

Page 7 - 1.0 Introduction

6.0 System Details15© Baxi Heating UK Ltd 20076.7 Sealed Systems (Fig. 13)1. SAFETY VALVE - A safety valve complying with therequirements of BS 6750 P

Page 8 - 2.0 General Layout

7.0 Site Requirements16© Baxi Heating UK Ltd 20077.1 LocationNOTE: Due to the high efficiency of the boiler aplume of water vapour will be discharged

Page 9 - 3.0 Appliance Operation

7.0 Site Requirements17© Baxi Heating UK Ltd 20077.3 Clearances (Figs. 15 &16)1. A flat vertical area is required for the installation of theboile

Page 10 - Hydraulic Resistance Chart

7.0 Site Requirements18© Baxi Heating UK Ltd 20077.6 Condensate DrainFAILURE TO INSTALL THE CONDENSATEDISCHARGE PIPEWORK CORRECTLY WILL AFFECTTHE RELI

Page 11 - 5.0 Dimensions and Fixings

7.0 Site Requirements19© Baxi Heating UK Ltd 2007NIIGFMIAAFHJ,KDEHLikely flue positions requiring a flue terminal guard CRAIJ,KILSBTU7.7 FlueNOTE: Due

Page 12 - 6.0 System Details

2© Baxi Heating UK Ltd 2007Natural GasPotterton Promax 12 SLG.C.No41 591 79Potterton Promax 15 SLG.C.No41 591 87Potterton Promax 18 SLG.C.No41 591 80P

Page 13

8.0 Flue Options20© Baxi Heating UK Ltd 20078.1 Horizontal Flue SystemsConcentricThe maximum equivalent lengths are 4m (horizontal) or(vertical). Thei

Page 14

8.0 Flue Options21© Baxi Heating UK Ltd 2007Y8.2 Twin & Vertical Flue SystemsConcentricThe maximum equivalent lengths are 4m (vertical). Theirleng

Page 15

8.0 Flue Options22© Baxi Heating UK Ltd 2007Key Accessory Size Code NoFLUE GROUP BConcentric Flue System 110mm diameterA1 Horizontal Flue Terminal 850

Page 16 - 7.0 Site Requirements

8.0 Flue Options23© Baxi Heating UK Ltd 2007Vertical FlueAdaptorGasket8.4 For Vertical Flue Systems1. Undo the screws securing the blanking plate to t

Page 17

8.0 Flue Options24© Baxi Heating UK Ltd 20078.6 For Roof Terminals1. In the case of a pitched roof 25 - 50 degrees, positionthe lead tile to replace/f

Page 18

9.0 Plume Displacement25© Baxi Heating UK Ltd 20079.1 Plume Displacement Kit (P.D.K.)Kit No 5121371Content of kit1 70/110 Concentric Flue1 1m 70 Dia E

Page 19 - Property Boundary Line

9.0 Plume Displacement26© Baxi Heating UK Ltd 200710246810121470Ø Exhaust (metres)Concentric 70/110 Flue (metres)016182342012, 15, 18 & 2430 22242

Page 20 - 8.0 Flue Options

9.0 Plume Displacement27© Baxi Heating UK Ltd 20079.3 General Fitting Notes - P.D.K.1. Cut a hole in the external wall which the horizontalconcentric

Page 21

9.0 Plume Displacement28© Baxi Heating UK Ltd 2007500mm Min.Plume OutletElbow200mm Min.9.3 General Fitting Notes - P.D.K. (cont.)16. For aesthetic pur

Page 22

10.0 Installation29© Baxi Heating UK Ltd 2007Check Site Requirements (section 7) beforecommencing.10.1 Initial PreparationThe gas supply, gas type and

Page 23

Installer Notification Guidelines3© Baxi Heating UK Ltd 2007Choose BuildingRegulations NotificationRouteContact your relevant LocalAuthority Building

Page 24

10.0 Installation30© Baxi Heating UK Ltd 200710.2 Preparing The Boiler1. Remove the outer carton and packaging.2. Lift the outercase upwards and remov

Page 25 - 9.0 Plume Displacement

10.0 Installation31© Baxi Heating UK Ltd 200710.3 Fitting The Boiler (Fig. 24)1. Obtain retaining bracket and two M6 nuts from fittingbag.2. Offer up

Page 26

10.0 Installation32© Baxi Heating UK Ltd 200710.6 Making the Gas Connection1. Connect the gas supply to the G1/2(1/2in BSPTInternal) gas tap. This is

Page 27

10.0 Installation33© Baxi Heating UK Ltd 200710.7 Fitting the Flue (Cont)6. Ensure the inner flue support bracket is positioned inthe flue (Fig. 28).7

Page 28 - 500mm Min

10.0 Installation34© Baxi Heating UK Ltd 200710.8 Making The Electrical ConnectionsWARNING: This appliance must be earthed1. The electrical connection

Page 29 - 13.5 27.5 55 82.5 110

11.0 Electrical35© Baxi Heating UK Ltd 200711.1 Schematic Wiring DiagramKey To Wiring Colours b - Bluebk - Blackw - Whitebr - Browngy - Greyr - Redg -

Page 30 - 10.0 Installation

11.0 Electrical36© Baxi Heating UK Ltd 2007Wiring Keyb - Bluebk - Blackbr - Brownr - Redw - Whiteg/y - Green/Yellowg - Greengy - Greyop - Opaquey - Ye

Page 31

12.0 Commissioning the Boiler37© Baxi Heating UK Ltd 200712.1 Commissioning the Boiler1. Reference should be made to BS 5449 Section 5 whencommissioni

Page 32

13.0 Fitting the Outer Case38© Baxi Heating UK Ltd 200713.1 Fitting The Outer Case1. Position the outercase over the boiler engaging thelugs in the si

Page 33

14.0 Servicing the Boiler39© Baxi Heating UK Ltd 200714.1 Annual ServicingIf a combustion analyser is available the CO/CO2 can bechecked (for levels s

Page 34

Legislation4© Baxi Heating UK Ltd 2007This company declares that no substances harmfulto health are contained in the appliance or usedduring appliance

Page 35 - 11.0 Electrical

14.0 Servicing the Boiler40© Baxi Heating UK Ltd 200714.1 Annual Servicing (Cont)10. To clean the heat exchanger and burner proceed asfollows:a) Disco

Page 36

15.0 Changing Components41© Baxi Heating UK Ltd 200715.1 Changing ComponentsIMPORTANT: When changing components ensurethat both the gas and electrical

Page 37 - 12.0 Commissioning the Boiler

15.0 Changing Components42© Baxi Heating UK Ltd 200715.3 Flowswitch (Fig. 47)1. Drain the boiler (see Section 15.1 paragraph 2 & 3).2. Remove the

Page 38 - 13.0 Fitting the Outer Case

15.0 Changing Components43© Baxi Heating UK Ltd 200715.4 PCB (Figs. 48 & 49)WARNING: The PCB Control and FanAssembly are 325 Vdc. Isolate at suppl

Page 39 - 14.0 Servicing the Boiler

15.0 Changing Components44© Baxi Heating UK Ltd 2007The fan and venturi, gas valve, injector pipe,condensate trap, fan protection sensor, spark andsen

Page 40

15.0 Changing Components45© Baxi Heating UK Ltd 2007The removal of the fan is necessary to enable thechanging of the injector pipe, condensate trap an

Page 41 - 15.0 Changing Components

15.0 Changing Components46© Baxi Heating UK Ltd 2007The burner and heat exchanger can be changed afterremoval of the combustion box door. To change th

Page 42

15.0 Changing Components47© Baxi Heating UK Ltd 2007Combustion Box BaseCentral Insulation PanelSupport BracketBurner15.12 Heat Exchanger Lower Insulat

Page 43

16.0 Short Parts List48© Baxi Heating UK Ltd 2007Short Parts ListKey G.C. Description ManufacturersNo. No. Part No.A E06 058 Flow TemperatureThermisto

Page 44

17.0 Fault Finding49© Baxi Heating UK Ltd 2007LowHighResetONMains OnLED Light(Green)Boiler OnLED Light(Green)LockoutLED Light(Red)LightsOff Off Off

Page 45

Safe Manual Handling5© Baxi Heating UK Ltd 2007GeneralThe following advice should be adhered to, from when first handling the boiler to the final stag

Page 46

17.0 Fault Finding50© Baxi Heating UK Ltd 2007No Switched Live toboiler. Check SystemsControls and SystemWiring.240V at B ?Check wiring fromterminal b

Page 47

17.0 Fault Finding51© Baxi Heating UK Ltd 2007DRY-FIRENOFill system with water andbleed out all air.Replace PCB.YESNOYESNOIs the system full of water

Page 48 - 16.0 Short Parts List

17.0 Fault Finding52© Baxi Heating UK Ltd 2007IGNITION LOCKOUTYESIs there gas at gas valve inlet?Check isolation valve andgas supply.YESNOReset Lockou

Page 49 - 17.0 Fault Finding

17.0 Fault Finding53© Baxi Heating UK Ltd 2007OVERHEAT LOCKOUTReplace Stat.Replace Stat.Wiring from PCB tothermostats faulty.YESNOYESNONODisconnectbla

Page 50

17.0 Fault Finding54© Baxi Heating UK Ltd 2007FAN LOCKOUTRectify wiring.NOYESUnplug3-way PCB connector& unplug fan. Is therecontinuity from N to O

Page 51

17.0 Fault Finding55© Baxi Heating UK Ltd 2007THERMISTORReplace thermistor.Wiring from PCB tothermistor faulty.YESNONOYESReplace PCB.Unplugthermistor,

Page 52

18.0 Notes56© Baxi Heating UK Ltd 2007

Page 53

18.0 Notes57© Baxi Heating UK Ltd 2007

Page 54

CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxesTIME & TEMPERATURE CONTROL TO HEATING

Page 55

SERVICE 1DATEENGINEER NAMECOMPANY NAMETEL No.CORGI ID CARD SERIAL No.COMMENTSSIGNATURESERVICE 2DATEENGINEER NAMECOMPANY NAMETEL No.CORGI ID CARD SERIA

Page 56 - 18.0 Notes

© Baxi Heating UK Ltd 20071.0 Introduction 72.0 General Layout 83.0 Appliance Operation 94.0 Technical Data 105.0 Dimensions and Fixings 116.0 System

Page 57

© Baxi Heating UK Ltd 2007Comp No5121908 - Iss 2 - 9/07POTTERTONA Trading Division of Baxi Heating UK Ltd (3879156)Adivision of Baxi GroupBrooks House

Page 58 - COLLECTIVE MARK

1.1 Description1. The Potterton Promax SL range are gas fired roomsealed fan assisted condensing central heating boilers.2. The maximum output of the

Page 59

2.0 General Layout8© Baxi Heating UK Ltd 20072.1 Layout (Figs. 3,4,5 & 6)1. Wall Plate2. Flue Elbow3. Heat Exchanger4. Burner5. Air Box6. Fan Prot

Page 60 - 5121908 - Iss 2 - 9/07

3.0 Appliance Operation9© Baxi Heating UK Ltd 20073.11. Switched Live On: When the switched live switcheson if the flow temperature is less than the s